Product Center
  •  PR Electronics transmitter 9116B

PR Electronics transmitter 9116B

Brand: PR Electronics

Product model: PR Electronics 9116B
Product Description:

PR Electronics Transmitter 9116B - PR Electronics industrial signal regulator manufacturer recommends: 5337 temperature transmitter, 4104 universal signal transmitter, 3117 bipolar isolation converter, 3118 isolation converter / divider, 9116 general purpose converter (SIL), 4511 communication programming interface.

  • Product introduction
  • Detailed parameters
  • Product application
  • Data download

PR Electronics Transmitter 9116B - PR Electronics industrial signal regulator manufacturer recommends: 5337 temperature transmitter, 4104 universal signal transmitter, 3117 bipolar isolation converter, 3118 isolation converter / divider, 9116 general purpose converter (SIL), 4511 communication programming interface.

Universal transmitter
RTD, TC, Ohm, potentiometer, mA and V signal input
Two wire transmitter power supply
Active / passive mA output and relay output
Allow independent power supply or power guideway power supply, such as PR 9400
SIL 2 certification through comprehensive assessment

 PR Electronics transmitter 9116B - PR Electronics

Advanced functions
Adjust and display process parameters (PR 4501/4511) through removable display panels, and calibrate and simulate process signals.
Relay functions are advanced settings, such as setting switch points, window functions, delay, sensor failure and power failure.
Copy parameters between products through 4501 removable display panels.
Reduced active input signal Uo Ex parameter < 8,3 V.
Internal or external CJC compensation is used to improve TC measurement accuracy.
Active and passive mA output is achieved through the same terminal.

PR Electronics Transmitter 9116B - PR Electronics industrial signal regulator manufacturer

environment condition
Working temperature -20 to C +60 to C
Storage temperature -20 to C +85 to C
Calibration temperature 20... 28 degree C
Relative humidity < 95% RH (no condensation)
Protection level IP20
Installation condition pollution level 2 & amp; measurement / overvoltage level II
Mechanical specifications
Structural dimensions (high x width x deep) 109 x 23,5 x 104 mm
Structural dimension (high x width x deep) - installed 4501 / 4511 time 109 x 23,5 x 116 / 131 mm
Weight (about) 185 G
Weight (contains 4501 / 4511) 200 g / 215 G
DIN rail type DIN EN 60715/35 mm
Wire specification 0,13... 2,08 mm2 / AWG 26... 14 stranded wire
Screw terminal torque 0,5 Nm
Anti vibration specification IEC 60068-2-6
2... 13.2 Hz + 1 mm
13.2... 100 Hz + 0,7 G
Common specifications
Power Supply
Power supply voltage 19,2... 31,2 VDC
Fuses 1,25 A SB / 250 VAC
The maximum power consumption is less than 2,1 W
The maximum power consumption is less than 1,7 W
Isolation voltage
Test / work: 2,6 kVAC / 300 VAC enhanced isolation between input and all other components
2,6 kVAC / 300 VAC enhanced isolation between analog output and power supply
1,5 kVAC / 150 VAC enhanced isolation between state relays and power supplies
response time
Temperature input can be set (0... 90%, 100... 10%) 1... 60 s
MA / V input (set) 0,4... 60 s
Auxiliary power supply
9116B1: 2 wire power supply (terminal 54... 52) 28... 16,5 VDC / 0... 20 mA
9116B2: 2 wire power supply (terminal 54... 52) 21,4... 16,5 VDC / 0... 20 mA
Signal dynamic range, input 24 bit
Signal dynamic range, output 16 bit
The minimum signal to noise ratio is 60 dB (0... 100 kHz).
The accuracy is better than the range set by 0,1%.
Input specification
RTD input
RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance 50 (max)
Sensor current rating 0,2 mA
Effect of sensor cable resistance on accuracy (3-/4- line) < 0002 ohm / Omega
Sensor fault detection can be set ON / OFF
Short circuit detection Yes
TC input
Thermocouple models B, E, J, K, L, N, R, S, T, U, W3, U,
Cold junction compensation (CJC), through the built-in sensor connector 5910 to achieve external compensation 20... 28 degrees C or less than 1 C, -20... 20 degrees C / 28... 70 degrees C or less 2 degrees C
Cold junction compensation (CJC), internal compensation is achieved by built-in sensor (2,0 + C + 0,4 degree C * * t).
T = internal temperature environment temperature
Current input
Measurement range 0... 23 mA
Adjustable measurement range 0... 20 and 4... 20 mA
Input resistance is 20 + PTC 50 ohm.
Sensor fault detection 4... 20 mA circuit break
Voltage input
Measurement range 0... 12 VDC
The measuring range can be set 0/0,2... 1, 0/1... 5, 0/2... 10 VDC.
Input resistance is >10 M ohm.
Output specification
Current output
Signal range 0... 23 mA
Set signal range 0... 20/4... 20/20... 0/20... 4 mA
The load (@ current output) is less than 600 ohm.
Load stability less than 0,01% set range / 100 Omega
Sensor failure alarm output 0 / 3,5 / 23 mA / none
Upper / lower limit current 23 mA / 3,5 mA conforming to NAMUR NE43 standard
The current limit is less than 28 mA
Passive two-wire mA output
Maximum external 2 wire power supply 26 VDC
Maximum load resistance [O] (Vsupply-3,5) /0023 A
Effect of external 2 wire power supply voltage < 0005% set range / V
Relay output
Relay function switch point, window function, sensor fault alarm, power on and power off state indication.
Max voltage 250 VAC / VDC
Maximum current 2 A
Maximum AC power 500 VA
Max. DC current, resistive load is less than 30 VDC 2 ADC
Max. DC current, resistive load > 30 VDC please see the manual description.
Status relay
Maximum voltage 110 VDC / 125 VAC
Maximum current 0,3 ADC / 0,5 AAC
Maximum AC power 62,5 VA / 32 W
Meet the standards
EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
Authentication
ATEX 2014/34/EU KEMA 10ATEX0053 X
IECEx KEM 10.0022X
FM 3038267-C
INMETRO DEKRA 16.0004 X
UL UL 61010-1
EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410
CCOE P337349/4
DNV-GL Marine Stand. f. Certific. No. 2.4
ClassNK TA18527M
SIL SIL 2 Certification & comprehensive assessment in line with IEC 61508 standard

PR Electronics Transmitter 9116B - PR Electronics industrial signal regulator manufacturer

application
9116B can be installed in the security area or zone 2 / Cl. 1, Div 2 area, and can receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. Gr. area signal.
Temperature, voltage, potentiometer and linear resistance input signal measurement.
Power supply and signal isolation of 2 wire transmitter.
Product and sensor fault alarm can be indicated through independent status relay or power guide.
9116 design, development and certification according to the requirements of IEC 61508, in line with SIL 2 application requirements.
Technical characteristics
1 green and 1 red front LED lights indicate normal operation and malfunction, and 1 yellow LED lights indicate relay status.
2,6 kVAC electrical isolation (input / output / power port).
Installation and commissioning
Standard vertical or horizontal DIN guide rail installation, no need to install clearance.