  •  PR Electronics transmitter 5337D temperature transmitter

PR Electronics transmitter 5337D

Brand: PR Electronics

Product model: PR Electronics 5337D
Product Description:

PR Electronics Transmitter 5337D temperature transmitter - PR Electronics industrial signal conditioning module manufacturer, recommended products: 5337 temperature transmitter, 4104 universal signal transmitter, 3117 bipolar isolation converter, 3118 isolation converter / divider, 9116 general purpose converter (SIL), 4511 communication programming interface.

  • Product introduction
  • Detailed parameters
  • Product application
  • Data download

PR Electronics Transmitter 5337D temperature transmitter - PR Electronics industrial signal conditioning module manufacturer, recommended products: 5337 temperature transmitter, 4104 universal signal transmitter, 3117 bipolar isolation converter, 3118 isolation converter / divider, 9116 general purpose converter (SIL), 4511 communication programming interface.

Two wire HART transmitter

RTD, TC, Ohm and bipolar mV signal input
Two analog input and five device variables (with state variables)
HART 5 or HART 7 protocol version switch
Hardware evaluation that meets SIL application requirements
Installed in hazardous gas and dust area.

 PR Electronics transmitter 5337D temperature transmitter

Technical characteristics
HART 5 or HART 7 protocol version can be adjusted by parameter switching.
HART 7 provides:
The long name can be up to 32 characters.
Enhanced Burst Mode and event notification with time tags.
The device variables and states can be mapped to any dynamic variable PV, SV, TV or QV.
Process signal trend measurement with recording and summarizing data.
Automatic event notification with time tags.
The instruction set with higher communication efficiency.
5337D is designed according to strict safety requirements, so it is suitable for SIL installation applications.
Continuous monitoring of important data to ensure the safety of use.
In line with the requirements of NAMUR NE21, the 5337 HART transmitter can provide top-level measurement performance in harsh EMC environment. In addition, 5337D also meets the requirements of NAMUR NE43 and NE89 standards.
Installation and commissioning
Standard DIN B sensor head mounted.
Set parameters through standard HART or PR 5909 communicator.

PR Electronics Transmitter 5337D temperature transmitter - PR Electronics industrial signal regulator manufacturer

environment condition
Working temperature -40 to C +85 to C
Calibration temperature 20... 28 degree C
Relative humidity < 95% RH (no condensation)
Protection level (enclosure / terminal) IP68 / IP00
Mechanical specifications
Structural dimensions o 44 x 20,2 mm
Weight (about) 50 g
Conductor specification 1 x 1,5 mm2 stranded wire
Screw terminal torque 0,4 Nm
Anti vibration specification IEC 60068-2-6
2... 25 Hz + 1,6 mm
25... 100 Hz + 4 g
Common specifications
Power Supply
Power supply voltage 8,0... 30 VDC
Isolation voltage
Isolation voltage, test / work 1,5 kVAC / 50 VAC
response time
Response time (set) 1... 60 s
Voltage drop 8,0 VDC
Programming Loop Link & HART
Signal-to-noise ratio > 60 dB
The accuracy is better than the range set by 0,05%.
Signal dynamic range, input 22 bit
Signal dynamic range, output 16 bit
The effect of EMC electromagnetic compatibility on accuracy: < 0,1% set range
Effect of extended EMC electromagnetic compatibility on accuracy: NAMUR NE21, A criterion, burst < + 1% set range
Input specification
Common input specifications
The maximum offset is 50% of the maximum value of the selected input type.
RTD input
RTD type Pt50/100/200/500/1000; Ni50/100/120/1000
The resistance of the cable is 5 ohm (a single conductor can be as high as 50 ohms, provided that the measuring accuracy will be reduced).
Sensor current rating 0,2 mA
TC input
Thermocouple models B, E, J, K, L, N, R, S, T, U, W3, U,
Cold end compensation (CJC) fixed compensation, through the Pt100 or Ni100 sensor to achieve internal or external compensation.
Voltage input
Measurement range -800... +800 mV
Minimum measurement range (range) 2,5 mV
Input resistance 10 M ohm

Output specification
Current output
Signal range 4... 20 mA
Minimum signal range 16 mA
The load (@ current output) is less than (Vsupply - 8) / 0023 [Omega].
Sensor failure alarm output can be set 3,5... 23 mA
Upper / lower limit current 23 mA / 3,5 mA conforming to NAMUR NE43 standard
Common output specifications
Update time 440 MS
HART protocol version HART 7 and HART 5
Meet the standards
EMC 2014/30/EU
EAC TR-CU 020/2011
Authentication
ATEX 2014/34/EU KEMA 03ATEX1537
IECEx KEM 10.0083X
FM FM17US0013X
CSA 1125003
INMETRO DEKRA 18.0002X
EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410
DNV-GL Marine Stand. f. Certific. No. 2.4
SIL hardware evaluation that meets SIL application requirements

PR Electronics Transmitter 5337D temperature transmitter - PR Electronics industrial signal regulator manufacturer

application
TC or RTD sensors linearize temperature measurements, such as Pt100 and Ni100.
Two RTD or TC input signal single value, difference or average value 4... 20 mA analog output PV value, and HART communication.
The linear resistance is changed to a standard analog current signal, for example, a valve signal or an ohmic output liquid level meter.
Convert bipolar mV signal to standard 4... 20 mA current signal.
HART more than 7 point communication mode can be connected to up to 63 transmitters for digital communication.

ATEX Installation Drawing - 5337A
IECEx installation drawing - 5337A
ATEX Installation Drawing - 5337D
IECEx installation drawing - 5337D
FM Installation Drawing No. 5300Q502
CSA Installation Drawing No. 533XQC03